Application of closed-loop oscillating heat-pipe with check valves (CLOHP/CV) air-preheater  for reduced relative-humidity in drying systems

Abstract
This paper aims to design, construct, and test the CLOHP/CV air-preheater for reduced relative humidity in drying systems for recovering the waste heat from the drying cycle. The CLOHP/CV heat-exchanger consisted of 3.58 m long copper tubes, with an internal diameter of 0.002 m. The evaporator and condenser sections were 0.19 m long, the adiabatic sections were 0.08 m long, the hot-air velocities were 0.5, 0.75 and 1 m/s with the hot-air temperatures being 50, 60 and 70 C,and the relative humidity was 100%. The working fluid was R134a with the filling ratio of 50%. It can be concluded that, with an increase in the hot-air temperature from 50 to 70 C, the heat-transfer rate slightly increases. The velocity increases from 0.5, 0.75 to 1 m/s and the heat-transfer rate slightly decreases. The velocity increases from 0.5, 0.75 to 1 m/s and the effectiveness slightly decreases. The hot-air temperature increases from 50 to 70 C and the effectiveness slightly increases.
The relative humidity reduced to the range 54–72% from 89% to 100%. The CLOHP/CV air-preheater can reduce the relative humidity and achieve energy thrift.

责任编辑: banye 参与评论
本站地图|热管配套|企业邮局|产品说明

Copyright © 1996-2010 China Harbin DawnHappy Heat Pipe Technology Co., Ltd.
哈尔滨晨怡热管技术有限公司   电话:0451-82589558 82589508 82589538   传真:0451-82552085 技术支持:13704813968
地址:哈尔滨市南岗区南通大街256号  邮编:150001  电子信箱:heatpipe@yahoo.cn   heat-pipe@hotmail.com heat.pipe@yahoo.com.cn 
本站永久域名:http://china-heatpipe.net     http://heatpipe.net.cn    http://rg.nx8.net     http://nx8.net  
中华人民共和国信息产业部ICP/IP地址信息备案:黑ICP备07500228  哈尔滨市公安局国际联网备案登记:哈公网监备23010002001165

Powered By: KingCMS 3.0 Beta